TR-3 Transmitter for analog signal from strain gauge

Explanation
TR3 is a microprocessor based transmitter that processes strain gauge signals for industrial use.

It is used as a signal converter for PLC or similar industrial control devices in weighing, dosing, level control and process control applications. With an adjustable relay output, it is possible to control stand-alone automation systems, such as on-off, fill-empty.

The rail mounting housing forms integrity with other panel components and facilitates connections.

The device, designed for industrial environments, offers three-way galvanic isolation. This eliminates the risk of damage to strain gauges from leakage currents, and the output stability is not affected by electrical noise. Since all adjustments are made via buttons, the deviations that can occur with potentiometer elements are eliminated.

Features
• Three-way galvanic isolation
• Internal power supply for current output – eliminates the need for an external power supply
• Zero to 50% full scale adjustment
• Overvoltage error indicator
• Relay status indicator
• Output for current 0-20 mA
• Voltage output 10 V

Options
• RS232

Technical Parameter Value
Accuracy 0.03
A/D conversion 24-bit Sigma-Delta
Conversion Rate 50Hz-400Hz
Read Frequency 50Hz-400Hz
Output current (load) < 500 ohm
Output voltage (load) > 5k ohm
Strain gauges
Number of allowed strain gauges 8 pieces (350 ohm)
Analog input range 1 mV/V – 2 mV/V – 5 mV/V – 160 mV/V
Supply voltage 10V
Insulation Voltage
Power – Strain gauge 1.5 kV
Power – Output signal 1.5 kV
Strain gauge – Output signal 1.5 kV
Environment
Operating Temperature Range (OIML Approved) 0°C +50°C
Storage temperature range -20°C +70°C
Operating voltage and power 24V DC (18V … 36 V) – 5W
Control and Display
Keyboard 3 tactile buttons, 4-DIP switches
Weight Display
Function Display
Program indicator
Body
Material and Protection Class Rail mounting, plastic, IP20
Weight 0.1 kg
Package weight and dimensions 0.2 kg, 15x24x6 cm
Communication Standard
Options
Serial communication port output – RS-232
Output for parallel printer
Binary (BCD) output
Output for remote display
Digital I/O 1 relay output (2A)                        –
Analog output 4-20mA / 0-10V                                   –
The serial communication output and digital I/O options cannot be used at the same time.